Hilti Ventilated Cavity Barriers (CFS‑VB) E60 50 sizes 150–350 mm and E120 25 sizes 175–375 mm, with product codes 2395739, 2395750, 2395751, 2395754, 2395755, 2395756, 2395757, 2395759, 2395760, 2395761, 2395762, 2395763, 2395764, 2395165 and 2395766, are recalled. A manufacturing fault means the staples fixing the intumescent strip to the mineral wool may be insufficient, allowing partial detachment in fire and potentially reducing declared fire performance. Project managers and affected users should contact Hilti (GB) Limited on 0800 886 100 or gbhiltiproductquality@hilti.com for assistance.
What's being recalled
Product Recall for specific product codes and ranges of Hilti (GB) Limited Ventilated Cavity Barriers found not to consistently achieve the declared reaction to fire performance.
Type: Construction Products – Ventilated Cavity Barrier
Model: (CFS-VB) - E60 50 (Sizes 150-350mm) and E120 25 (sizes 175-375mm)
Product Codes: 2395739 2395750 2395751 2395754 2395755 2395756 2395757 2395759 2395760 2395761 2395762 2395763 2395764 2395165 2395766
Country of Origin: Slovenia
Product Description: Ventilated cavity barrier comprised of a mineral wool slab, intumescent strip(s) and GF reinforced PE foil.
How to identify it
PSD notification number: 2602-0235
Notified by: Office for Product Safety and Standards
The hazard
Hilti (GB) Limited have identified that, due to a manufacturing fault, the active component of the CFS-VB ventilated cavity barrier might not be properly attached. The staples used to fix the intumescent strip in place to the mineral wool component of the cavity barrier may not be of the required number. This may lead to partial detachment of the intumescent strip in the case of fire, potentially reducing the final fire performance of the cavity barrier.
What to do
Hilti (GB) Limited have issued a recall for a limited number of specific product codes and ranges of ventilated cavity barriers. Affected projects have been notified of the issue directly.
Hilti (GB) Limited’s team can be contacted on 0800 886 100 or gbhiltiproductquality@hilti.com for project managers with questions or requiring assistance.